Plc function object to BaseFcPPO3MotorAggr.
Connect the function object to an object of class or subclass of BaseFcPPO3MotorAggr.See also
BaseFcPPO3MotorAggr
RtBody attributes pwr_sClass_BaseFcPPO3MotorAggrFo | |||
Float32 |
RefSpeedExt |
REX | Analog input to control the speed reference to the converter in Auto mode. |
Float32 |
RefSpeedLoc |
RLO | Analog input to control the speed reference to the converter in Local mode. |
Boolean |
PowerInterlock |
pil | Interlock input for the contactor. If PowerInterlock is high, the order output is reset, and the mode is forced to Man. This force can be disabled by setting Mode.OpNoAutoToMan to 1. |
Boolean |
ExtControl |
eco | Controls the mode when extern mode control is selected, i.e. Mode.OpExtAndIntMan is set to 1. The Auto/Man buttons are then removed from the object graph, and the auto/man selection i performed by this input instead. If ExtControl is 1, mode is auto, and if ExtControl is 0 mode is manual. |
Boolean |
ExtStart |
est | Input to control the contactor order output in Auto mode. |
Boolean |
ExtInterlock |
ilk | Interlock input. If ExtInterlock is high, the order output is reset, and the mode is forced to Man. This force can be disabled by setting Mode.OpNoAutoToMan to 1. |
Boolean |
LocMode |
loc | Input to set Local mode. Normally connected to a switch on a local panel. |
Boolean |
OpLocStart |
lst | Input to control the contactor order output in local mode. Normally connected to a button on a local panel. |
Boolean |
ResTrip |
trp | Input to reset the trip run time measurement. Se the class RunTimeCounter. |
Boolean |
DisableSup |
dis | Disable supervision. Alarm messages are suppressed. |
AttrRef |
PlcConnect |
The main object connected to this function object. | |
Boolean |
On |
on | Output for drive started, from converter statusword SW bit 2. |
Boolean |
Err |
err | Error output. The output it high when the object is interlocked, or when components alarms or has tripped. Can be used to reset orders on the start inputs ExtStart and OpLocalStart to avoid unwanted restarts after fault. |
DevBody attributes | |||
pwrs:Class-$PlcNode |
PlcNode |
GraphPlcNode | |
object_type |
11 |
parameters[0] |
10 |
parameters[1] |
1 |
parameters[2] |
9 |
parameters[3] |
0 |
subwindows |
1 |
subwindow_class[0] |
pwrb:Class-WindowPlc |
graphmethod |
0 (standard, individual attributes) |
graphindex |
0 |
default_mask[0] |
255 |
default_mask[1] |
3 |
segname_annotation |
1 |
compmethod |
58 |
compindex |
0 |
tracemethod |
0 |
traceindex |
0 |
connectmethod |
10 |
executeordermethod |
2 |
objname |
FcPPO3MAggrFo |
graphname |
FcPPO3MAggrFo |
Template Object |
Type Float32
Flags Noinvert
GraphName REX
Body RtBody
Class $Input
Description
Analog input to control the speed reference to the converter in Auto mode.
Type Float32
Flags Noinvert
GraphName RLO
Body RtBody
Class $Input
Description
Analog input to control the speed reference to the converter in Local mode.
Type Boolean
Flags Noinvert
GraphName pil
Body RtBody
Class $Input
Description
Interlock input for the contactor. If PowerInterlock is high, the order output is reset, and the mode is forced to Man. This force can be disabled by setting Mode.OpNoAutoToMan to 1.
Type Boolean
Flags Noinvert
GraphName eco
Body RtBody
Class $Input
Description
Controls the mode when extern mode control is selected, i.e. Mode.OpExtAndIntMan is set to 1. The Auto/Man buttons are then removed from the object graph, and the auto/man selection i performed by this input instead. If ExtControl is 1, mode is auto, and if ExtControl is 0 mode is manual.
Type Boolean
Flags Noinvert
GraphName est
Body RtBody
Class $Input
Description
Input to control the contactor order output in Auto mode.
Type Boolean
Flags Noinvert
GraphName ilk
Body RtBody
Class $Input
Description
Interlock input. If ExtInterlock is high, the order output is reset, and the mode is forced to Man. This force can be disabled by setting Mode.OpNoAutoToMan to 1.
Type Boolean
Flags Noinvert
GraphName loc
Body RtBody
Class $Input
Description
Input to set Local mode. Normally connected to a switch on a local panel.
Type Boolean
Flags Noinvert
GraphName lst
Body RtBody
Class $Input
Description
Input to control the contactor order output in local mode. Normally connected to a button on a local panel.
Type Boolean
Flags Noinvert
GraphName trp
Body RtBody
Class $Input
Description
Input to reset the trip run time measurement. Se the class RunTimeCounter.
Type Boolean
Flags Noinvert
GraphName dis
Body RtBody
Class $Input
Description
Disable supervision. Alarm messages are suppressed.
Type AttrRef
Flags
Body RtBody
Class $Intern
Description
The main object connected to this object. This attribute is set when the function object is connected from the plc editor by the connect function.
Type Boolean
Flags ReduTransfer|Noinvert
GraphName on
Body RtBody
Class $Output
Description
Output for drive started, from converter statusword SW bit 2.
Type Boolean
Flags ReduTransfer|Noinvert
GraphName err
Body RtBody
Class $Output
Description
Error output. The output it high when the object is interlocked, or when components alarms or has tripped. Can be used to reset orders on the start inputs ExtStart and OpLocalStart to avoid unwanted restarts after fault.
Type pwrs:Class-$PlcNode
Flags
Body DevBody
Class $Buffer
Description