Class BaseFcPPO3MotorAggrFo
Version 1.0
Modified 13-MAR-2008 14:16:02.23
Code PlcTemplate
 Plc function object to BaseFcPPO3MotorAggr.


 Connect the function object to an object of class or subclass of
 BaseFcPPO3MotorAggr.

See also



RtBody attributes pwr_sClass_BaseFcPPO3MotorAggrFo
Float32 RefSpeedExt REX Analog input to control the speed reference to the converter in Auto mode.
Float32 RefSpeedLoc RLO Analog input to control the speed reference to the converter in Local mode.
Boolean PowerInterlock pil Interlock input for the contactor.
If PowerInterlock is high, the order output is reset, and the mode
is forced to Man. This force can be disabled by setting Mode.OpNoAutoToMan
to 1.
Boolean ExtControl eco Controls the mode when extern mode control is selected, i.e.
Mode.OpExtAndIntMan is set to 1. The Auto/Man buttons are then removed
from the object graph, and the auto/man selection i performed by this
input instead.

If ExtControl is 1, mode is auto, and if ExtControl is 0 mode is manual.
Boolean ExtStart est Input to control the contactor order output in Auto mode.
Boolean ExtInterlock ilk Interlock input.
If ExtInterlock is high, the order output is reset, and the mode
is forced to Man. This force can be disabled by setting Mode.OpNoAutoToMan
to 1.
Boolean LocMode loc Input to set Local mode.
Normally connected to a switch on a local panel.
Boolean OpLocStart lst Input to control the contactor order output in local mode.
Normally connected to a button on a local panel.
Boolean ResTrip trp Input to reset the trip run time measurement.
Se the class RunTimeCounter.
Boolean DisableSup dis Disable supervision. Alarm messages are suppressed.
AttrRef PlcConnect   The main object connected to this function object.
Boolean On on Output for drive started, from converter statusword SW bit 2.
Boolean Err err Error output.
The output it high when the object is interlocked, or when components
alarms or has tripped. Can be used to reset orders on the start inputs
ExtStart and OpLocalStart to avoid unwanted restarts after fault.

DevBody attributes 
pwrs:Class-$PlcNode PlcNode  


GraphPlcNode
object_type 11
parameters[0] 10
parameters[1] 1
parameters[2] 9
parameters[3] 0
subwindows 1
subwindow_class[0] pwrb:Class-WindowPlc
graphmethod 0 (standard, individual attributes)
graphindex 0
default_mask[0] 255
default_mask[1] 3
segname_annotation 1
compmethod 58
compindex 0
tracemethod 0
traceindex 0
connectmethod 10
executeordermethod 2
objname FcPPO3MAggrFo
graphname FcPPO3MAggrFo


Template Object


Attributes detail


RefSpeedExt Input
Class Input
Type Float32
Flags Noinvert
GraphName REX
Body RtBody
 Analog input to control the speed reference to the converter in Auto mode.

RefSpeedLoc Input
Class Input
Type Float32
Flags Noinvert
GraphName RLO
Body RtBody
 Analog input to control the speed reference to the converter in Local mode.

PowerInterlock Input
Class Input
Type Boolean
Flags Noinvert
GraphName pil
Body RtBody
 Interlock input for the contactor.
 If PowerInterlock is high, the order output is reset, and the mode
 is forced to Man. This force can be disabled by setting Mode.OpNoAutoToMan
 to 1.

ExtControl Input
Class Input
Type Boolean
Flags Noinvert
GraphName eco
Body RtBody
 Controls the mode when extern mode control is selected, i.e.
 Mode.OpExtAndIntMan is set to 1. The Auto/Man buttons are then removed
 from the object graph, and the auto/man selection i performed by this
 input instead.

 If ExtControl is 1, mode is auto, and if ExtControl is 0 mode is manual.

ExtStart Input
Class Input
Type Boolean
Flags Noinvert
GraphName est
Body RtBody
 Input to control the contactor order output in Auto mode.

ExtInterlock Input
Class Input
Type Boolean
Flags Noinvert
GraphName ilk
Body RtBody
 Interlock input.
 If ExtInterlock is high, the order output is reset, and the mode
 is forced to Man. This force can be disabled by setting Mode.OpNoAutoToMan
 to 1.

LocMode Input
Class Input
Type Boolean
Flags Noinvert
GraphName loc
Body RtBody
 Input to set Local mode.
 Normally connected to a switch on a local panel.

OpLocStart Input
Class Input
Type Boolean
Flags Noinvert
GraphName lst
Body RtBody
 Input to control the contactor order output in local mode.
 Normally connected to a button on a local panel.

ResTrip Input
Class Input
Type Boolean
Flags Noinvert
GraphName trp
Body RtBody
 Input to reset the trip run time measurement.
 Se the class RunTimeCounter.

DisableSup Input
Class Input
Type Boolean
Flags Noinvert
GraphName dis
Body RtBody
 Disable supervision. Alarm messages are suppressed.

PlcConnect Intern
Class Intern
Type AttrRef
Flags
Body RtBody
 The main object connected to this object.
 This attribute is set when the function object is connected from
 the plc editor by the connect function.

On Output
Class Output
Type Boolean
Flags ReduTransfer|Noinvert
GraphName on
Body RtBody
 Output for drive started, from converter statusword SW bit 2.

Err Output
Class Output
Type Boolean
Flags ReduTransfer|Noinvert
GraphName err
Body RtBody
 Error output.
 The output it high when the object is interlocked, or when components
 alarms or has tripped. Can be used to reset orders on the start inputs
 ExtStart and OpLocalStart to avoid unwanted restarts after fault.

PlcNode Buffer
Class Buffer
Type pwrs:Class-$PlcNode
Flags
Body DevBody