Class BaseFcPPO3Fo
Version 1.0
Modified 13-MAR-2008 14:08:12.62
Code PlcTemplate
 Plc function object to BaseFcPPO3.


 Connect the function object to an object of class or subclass of
 BaseFcPPO3.

See also



RtBody attributes pwr_sClass_BaseFcPPO3Fo
Boolean PowerOn pwo Input for power on. When PowerOn is set the converter should
respond and be ready within the PowerUpTime (default 15 s).
During startup the converter status indications are flashing.
PowerOn also turns on the alarm supervision of the converter.

The object will work, even is this input isn't connected, but
will be no alarm when the communication is lost.
Boolean Start sta Input for start order (run) to the converter.
This will set first bit in the the controlword CW (On/Off1). The converter will
start and stop with ordinary ramps configured in the converter.
Float32 RefSpeed REF Analog input for the reference speed.
The value will be transfered in the O_REF field to the converter.
The O_REF ChanAo contains the the range attributes to convert the signal.
Boolean NoOff2 nof2 Input to stop the converter with coast stop, when the value is set to 0.
Sets the second bit in the control word CW, Off2.
Default value 1. Normally not used.
Boolean NoOff3 nof3 Input to stop the converter with emergency stop, when the value is set to 0.
Sets the third bit in the control word CW, Off3.
Default value 1. Normally not used.
Boolean EnableOperation eno Input for enable operation to the converter. Normally not used.
Boolean SupDisabled dis
AttrRef PlcConnect   The main object connected to this function object.
Boolean ReadyRemote rdy Output set when the converter is started, in remote control and ready
for remote order.
Boolean Run run Output set when the drive is started. From status world SW bit 2.

DevBody attributes 
pwrs:Class-$PlcNode PlcNode  


GraphPlcNode
object_type 11
parameters[0] 7
parameters[1] 1
parameters[2] 2
parameters[3] 0
subwindows 1
subwindow_class[0] pwrb:Class-WindowPlc
graphmethod 0 (standard, individual attributes)
graphindex 0
default_mask[0] 7
default_mask[1] 3
segname_annotation 1
compmethod 58
compindex 0
tracemethod 0
traceindex 0
connectmethod 10
executeordermethod 2
objname BaseFcPPO3Fo
graphname BaseFcPPO3Fo


Template Object
NoOff2 1
NoOff3 1
EnableOperation 1


Attributes detail


PowerOn Input
Class Input
Type Boolean
Flags Noinvert
GraphName pwo
Body RtBody
 Input for power on. When PowerOn is set the converter should
 respond and be ready within the PowerUpTime (default 15 s).
 During startup the converter status indications are flashing.
 PowerOn also turns on the alarm supervision of the converter.

 The object will work, even is this input isn't connected, but
 will be no alarm when the communication is lost.

Start Input
Class Input
Type Boolean
Flags Noinvert
GraphName sta
Body RtBody
 Input for start order (run) to the converter.
 This will set first bit in the the controlword CW (On/Off1). The converter will
 start and stop with ordinary ramps configured in the converter.

RefSpeed Input
Class Input
Type Float32
Flags Noinvert
GraphName REF
Body RtBody
 Analog input for the reference speed.
 The value will be transfered in the O_REF field to the converter.
 The O_REF ChanAo contains the the range attributes to convert the signal.

NoOff2 Input
Class Input
Type Boolean
Flags Noinvert
GraphName nof2
Body RtBody
 Input to stop the converter with coast stop, when the value is set to 0.
 Sets the second bit in the control word CW, Off2.
 Default value 1. Normally not used.

NoOff3 Input
Class Input
Type Boolean
Flags Noinvert
GraphName nof3
Body RtBody
 Input to stop the converter with emergency stop, when the value is set to 0.
 Sets the third bit in the control word CW, Off3.
 Default value 1. Normally not used.

EnableOperation Input
Class Input
Type Boolean
Flags Noinvert
GraphName eno
Body RtBody
 Input for enable operation to the converter. Normally not used.

SupDisabled Input
Class Input
Type Boolean
Flags Noinvert
GraphName dis
Body RtBody

PlcConnect Intern
Class Intern
Type AttrRef
Flags
Body RtBody
 The main object connected to this object.
 This attribute is set when the function object is connected from
 the plc editor by the connect function.

ReadyRemote Output
Class Output
Type Boolean
Flags ReduTransfer|Noedit|Noinvert
GraphName rdy
Body RtBody
 Output set when the converter is started, in remote control and ready
 for remote order.

Run Output
Class Output
Type Boolean
Flags ReduTransfer|Noedit|Noinvert
GraphName run
Body RtBody
 Output set when the drive is started. From status world SW bit 2.

PlcNode Buffer
Class Buffer
Type pwrs:Class-$PlcNode
Flags
Body DevBody